ALIAXIS PLX PIPE AND FITTINGS

What is the working Pressure of Aliaxis PLX pipe?

10 bar for the Primary pipe 4 bar for the Secondary containment pipe

What is the Aliaxis PLX pipe liner made of?

Ethylene Vinyl Alcohol (EVOH)

What is the difference between SDR11 and SDR17?

SDR = Standard Dimensional Ratio of Diameter to wall thickness eg: 110mm Diameter pipe with an SDR11 means 110 ÷11 = 10 This means the wall thickness is 10mm 110mm Diameter pipe with an SDR17 means 110 ÷17 = 6.5 This means the wall thickness is 6.5mm

What is the difference between PE80 and PE100?

PE80 & PE100 refer to the Minimum Required Strength over 50 years of the Polyethylene PE80 – MRS – 8.0 Mpa PE100 – MRS – 10.0 Mpa
EASY RISERS

At what height do you mount the Easy Riser knuckle joint?

The Knuckle joint needs to be mounted at approximately 1100mm from the ground. When you lay the Easy Riser over you need to be able to service the unit at a safe and comfortable height.

How high is the Aluminium tube?

Approximately 3.0m
FLEXIBLE CONNECTORS

What is the working Pressure of the Flexible connector?

50 PSI or 3.45 bar

What is the minimum bend radius?

1 ½” 115mm (4 ½”)
2” 152mm (6”)
LAFON PRESSURE REGULATOR VALVE

What Pressure can the valve operate at?

50 PSI or 3.45 bar

Can you adjust the valve?

Yes, you can adjustment screw located in the bottom of the unit. Remove the plug to access adjustment screw.

What is the maximum flow rate?

83 Litres per minute
SGB LEAK DETECTION

How do you reset the Leak Detector?

Pressing the “audible alarm signal” button will silence the alarm.

How do you stop the pump from continually running?

First close all valves on the manifold block (if fitted) If the pump does not stop quickly this is a sign that the pump may be damaged.